Please use this identifier to cite or link to this item:
https://repositorio.ufpe.br/handle/123456789/67115
Share on
Full metadata record
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.advisor | SIMÕES, Francisco Paulo Magalhães | - |
| dc.contributor.author | BATTISTI, Felipe de Melo | - |
| dc.date.accessioned | 2025-12-11T16:32:35Z | - |
| dc.date.available | 2025-12-11T16:32:35Z | - |
| dc.date.issued | 2025-06-30 | - |
| dc.identifier.citation | BATTISTI, Felipe de Melo. Addressing Real-World variability in power line inspections with unsupervised visual anomaly detection. 2025. Dissertação (Mestrado em Ciência da Computação) - Universidade Federal de Pernambuco, Recife, 2025. | pt_BR |
| dc.identifier.uri | https://repositorio.ufpe.br/handle/123456789/67115 | - |
| dc.description.abstract | Adetecção visual de anomalias em infraestruturas de transmissão de energia elétrica é fundamental para prevenir falhas críticas e garantir a confiabilidade da rede. À medida que essas redes se expandem para regiões remotas e complexas, inspeções manuais tradicionais enfrentam desafios operacionais, como alto custo, riscos à segurança e baixa escalabilidade. Embora métodos recentes de inspeção visual automatizada baseados em deep learning apresentem avanços, a maioria é avaliada em cenários controlados, o que limita sua eficácia em aplicações reais. Oproblema central abordado neste trabalho é a baixa capacidade de generalização de modelos não supervisionados de detecção de anomalias quando aplicados a imagens aéreas obtidas em condições reais de inspeção. Modelos supervisionados exigem grandes volumes de dados anotados com falhas raras e variadas—algo impraticável nesse domínio. Por isso, métodos não supervisionados, que aprendem apenas a partir de dados normais, são mais viáveis, mas enfrentam dificuldades ao lidar com ruído de fundo, variações de iluminação e anomalias sutis. Este trabalho demonstra que a integração de mecanismos de atenção e técnicas de remoção de fundo pode aprimorar significativamente a detecção de anomalias em cenários não controlados. Para isso, foi desenvolvido o InsPLAD-seg, um novo conjunto de dados com anotações em nível de pixel de falhas reais. Além disso, foram aplicados módulos de atenção (SENet e CBAM) e segmentação por objetos utilizando YOLO, com o objetivo de refinar a extração de características e reduzir interferências visuais. Os resultados mostram que a combinação de atenção e remoção de fundo melhora consistentemente os escores de AUROC em níveis de imagem e pixel, com destaque para a detecção de corrosões e pequenas falhas. Modelos como RD++ e DifferNet, aprimorados com atenção, alcançaram desempenho de ponta, enquanto a remoção de fundo aumentou a robustez frente à variabilidade visual. Esses achados reforçam que mecanismos de atenção e pré-processamentos que simulam condições controladas são essenciais para aproximar os modelos de detecção do uso prático em campo. Ao modelar diretamente anomalias em inspeções reais, esta abordagem contribui para sistemas de monitoramento mais robustos e escaláveis. Este trabalho viabiliza a aplicação prática de modelos de detecção de anomalias em ambientes ruidosos, nos quais precisão e escalabilidade são requisitos críticos. | pt_BR |
| dc.language.iso | por | pt_BR |
| dc.publisher | Universidade Federal de Pernambuco | pt_BR |
| dc.rights | openAccess | pt_BR |
| dc.rights.uri | https://creativecommons.org/licenses/by-nc-nd/4.0/ | pt_BR |
| dc.subject | Anomaly detection | pt_BR |
| dc.subject | Unsupervised learning | pt_BR |
| dc.subject | Industrial inspection | pt_BR |
| dc.subject | Power transmission | pt_BR |
| dc.subject | Deep learning | pt_BR |
| dc.title | Addressing Real-World variability in power line inspections with unsupervised visual anomaly detection | pt_BR |
| dc.type | masterThesis | pt_BR |
| dc.contributor.advisor-co | TEICHRIEB, Veronica | - |
| dc.contributor.authorLattes | http://lattes.cnpq.br/5204263811430063 | pt_BR |
| dc.publisher.initials | UFPE | pt_BR |
| dc.publisher.country | Brasil | pt_BR |
| dc.degree.level | mestrado | pt_BR |
| dc.contributor.advisorLattes | http://lattes.cnpq.br/4321649532287831 | pt_BR |
| dc.publisher.program | Programa de Pos Graduacao em Ciencia da Computacao | pt_BR |
| dc.description.abstractx | Visual anomaly detection in power transmission infrastructure is essential for preventing critical failures and ensuring grid reliability. As electricity networks expand into remote and complex environments, traditional manual inspections face significant challenges, including labor intensity, safety hazards, and limited scalability. Recent progress in deep learning has enabled automated visual inspection, but most anomaly detection models are evaluated under controlled conditions, limiting their real-world applicability. The key problem addressed is the poor generalization of unsupervised anomaly detectors when deployed on aerial images from real-world inspections. Supervised models require large, labeled datasets of rare and diverse defect types, something infeasible in power line inspection due to the scarcity and unpredictability of faults. Unsupervised methods, which learn only from normal data, are more suitable but struggle with cluttered backgrounds, variable lighting, and subtle anomaly patterns. This work shows that the integration attention mechanisms and background removal techniques enhances the detection of unsupervised anomalies in uncontrolled scenarios. created a novel dataset, InsPLAD-seg, with pixel-level annotations of real-world defects and applied attention modules (SENet, CBAM) and YOLO-based object segmentation to refine feature extraction and reduce noise interference. Our results demonstrate that combining attention mechanisms with background removal consistently improves AUROC scores at both image and pixel levels, especially in corrosion detection and small defect localization. RD++ and DifferNet models enhanced with attention modules achieved state-of-the-art results, while background segmentation further improved robustness to environmental variability. These findings suggest that controlled-like preprocessing and feature-aware attention are critical to bridging the gap between laboratory benchmarks and real-world deployments in infrastructure inspection. By modeling in situ power line anomalies, this approach supports more resilient and scalable grid monitoring solutions. This enables real-world deployment of anomaly detection models in noisy environments, where precision and scalability are critical | pt_BR |
| dc.contributor.advisor-coLattes | http://lattes.cnpq.br/3355338790654065 | pt_BR |
| dc.contributor.advisorORCID | https://orcid.org/0000-0001-9368-2298 | - |
| dc.contributor.advisor-coORCID | https://orcid.org/0000-0003-4685-3634 | - |
| Appears in Collections: | Dissertações de Mestrado - Ciência da Computação | |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| DISSERTAÇÃO Felipe de Melo Battisti.pdf | 10.62 MB | Adobe PDF | ![]() View/Open |
This item is protected by original copyright |
This item is licensed under a Creative Commons License